The system will be turned on after a signal from the automatic fire detection system.
In case all doors are closed a pressure difference over all cracks and seams should be maintained between the stairwell and the connecting smoke compartment. An extra precondition is that the force to open a door (force on the heck) should not be higher than 100 Newton. So this means that the pressure on the door in the stairwell together with the force of the closer should not exceed 100 Newton. In general a design pressure of ca. 50 Pa can be selected.
In case a door is opened on the level of the fire between the stairwell and smoke compartment, a minimum air velocity should be maintained. For evacuation purposes the design velocity varies between the 0.5 and 1.0 m/s (Depending on the applicable regulations) For repressive purposes a design velocity of 2.0 m/s is required.